Indoor
Air Monitoring
Description
When
there is a potential for vapor intrusion, indoor air sampling is
considered by
many stakeholders to be the most definitive method of determining if
there is
actually a problem. If indoor air testing is not possible, the
alternative is
to take a subsurface soil gas sample below the home or commercial
establishment
(see description of sub-surface soil gas monitoring) and model
potential indoor
exposures. Ideally, indoor air testing, soil gas sampling, and ambient
(outdoor) air testing are conducted simultaneously to determine if
elevated
indoor air concentrations are from the subsurface, indoor sources, or
the
background outdoor air.
There are
several technologies for monitoring indoor air, including:
á Obtaining Grab Samples
á Real-Time and
Near-Real-Time Sampling
á Passive Sampling
Grab
Samples
The most
common methods for monitoring indoor air are through grab samples.
Summaª
Canisters are used most to collect samples, followed by Tedlar¨
Bags. Other
methods, such as carbon absorption tubes, are
gaining in popularity.
Summa
canisters are small airtight metal containers. The sampling canister is
sent to
the field under vacuum and certified leak-free. The canister fills with
air at
a fixed flow rate over a preset period of time with use of a flow
controller.
The appropriate preset period should be determined on a case-by-case
basis. For
example, in residential settings, the period is typically 24 hours. In
commercial and industrial settings, samples are normally collected over
8 hours
to correspond to an average workday. After the canister is filled, it
is sent
to an analytical laboratory under the appropriate chain-of-custody
protocol and
analyzed. Very low detection limits, in the subparts per billion
volume
(ppbv) range are possible.
Tedlar
bags are a suitable alternative to Summa canisters for volatile
organic compounds (VOCs) when the holding time is less than
two
weeks and concentrations are in the parts-per-million (by volume)
range. Tedlar
bags are made from polyvinylfluoride film. They require the use of an
air pump,
so proper pump calibration is critical. They are lighter and less
expensive
than canisters. However, some regulatory agencies may not accept
results.
Real-time
and Near-Real-Time Sampling
Real-time
and near real-time analyzers can be used to collect multiple samples
that can
locate problem structures, vapor migration routes into structures, and
volatile
sources inside the structures. Continuous analyzers that collect data
automatically over a period of time can sort out background scatter and
determine temporal variations both indoors and below ground (soil gas).
A variety
of real-time analyzers exist, including handheld logging instruments
(see Photo Ionization Detector),
automated Gas
Chromatographs (GC) and portable Mass Spectrometers (see Gas Chromatography/Mass Spectrometry
or GC/MS). Several
mobile laboratories offer analysis by GC/MS with selective ion
monitoring to
obtain accurate results measured in the subparts per billion by
volume
range.
U.S.
EPAÕs Trace Atmospheric Gas Analyzer (TAGA) is a self-contained
mobile
laboratory (van) capable of real-time sampling and analysis in the low
ppbv
level. This unit is outfitted with a long hose and vacuum pump that
allows the
operators to survey a building in real time and identifies interior
sources of
chemicals. The unit is equipped with several gas chromatographs to aid
in
identification and confirmation of analysis, and it can be equipped
with other
instruments such as portable GC/MS for organic compounds or X- Ray Fluorescence sensors
for inorganics
(metals). The TAGA unit can also carry equipment (e.g., Summa canisters, Tedlar
bags) for
quick on-board laboratory analysis to supplement the results of other
samples.
However, the cost ($10,000 per day) and limited availability of the
TAGA hinder
the use of this system.
Passive
Sampling
Passive
samplers, less commonly used for vapor intrusion assessments, are
similar to
those described in Passive Soil Gas Screening.
Samplers use an
adsorbent to capture VOCs over a set period of time. The samplers are
sent to a
laboratory for analysis. With some samplers, the rate of sorption
is controlled and thus reasonably known, and the average concentration
can be
estimated. In the qualitative samplers, the rate of sorption is not
controlled,
so the mass captured can only be related to concentration using other
relationships (such as air exchange rate, the geometry of the room,
etc.).
Passive sampling has several potential advantages over other methods,
including
lower cost, small size, and less disruption to building occupants.
Disadvantages include weaknesses in detecting semi-volatile
organic compounds (SVOCs) and less analytical precision.
Often
passive samplers are used to screen a building, and if a problem is
indicated,
other methods are used.
Limitations
and Concerns
It
is essential to use methods capable of measuring levels of
contamination at
health-based thresholds. For some common toxic vapors, such as trichloroethylene
and perchloroethylene (also known as tetrachloroethylene), those are in
the
parts per billion by volume range. Thus, hand held PIDs are generally
not
suitable.
Results
are usually reported in parts per billion by volume or micrograms per
cubic
meter (µg/m3). The conversion factor
between the
two units depends upon the molecular weight of the compound in question.
One-time
sampling results may not be representative of long-term average
concentrations.
As an added precaution, indoor air samples may be collected using two
scenarios: first with the building under an induced positive pressure
and
second with the building under negative pressure relative to the
sub-surface.
Under consistent positive building pressure, vapor intrusion is likely
to be
insignificant, and the indoor air concentrations are influenced only by
indoor
and outdoor vapor sources. Under an induced negative pressure, air will
flow
into the building from all discontinuities in the building envelope,
including
the subsurface, thus enabling one to calculate the relative
contribution from
the subsurface by the difference between the indoor air concentrations
measured
under positive and negative building pressure. In the eastern U.S. or
the
Midwest, this may be similar to testing in the summer and winter.
In
some instances the goal of the monitoring program may be to indicate
the worst
possible exposure, while in other instances the goal is to indicate
exposure
under normal conditions. Goals should be clearly defined because they
could
affect the timing and frequency of monitoring. For example, in colder
climates,
indoor air vapor concentrations may be increased due to high negative
pressure
from indoor heating (furnaces, etc.). There is some controversy whether
the
best approach to sampling indoors during is to leave heating and
ventilation
systems on or off. With the former, one can achieve data that reflects
what
occupants are exposed to. In the latter instance, data may reflect the
worst
exposure. In some instances, data has been collected with the heating
and
ventilation both on and off.
Indoor
air and ambient air concentrations tend to exhibit considerable degrees
of
variability over time and under different climatic conditions. For
example, in
northern climates frozen ground may limit vertical flow of vapors, thus
increasing the lateral flow under buildings. Increased moisture due to
rainfall
and snowmelt may also serve to drive vapors into the relatively dry
soils under
a building.
Where
it is possible, sample locations should be selected in breathing zones
and
around potential preferential pathways. Concentrations within a
building are
typically higher in the lower level. Therefore, indoor air samples
should be
collected in the basement, if present, or on the first floor. If there
are
pathways within a building that may induce vapors to flow to upper
floors (e.g., elevator shafts), these
should be
sampled.
There
is a wide variation in building sizes, features, and age that will
influence
the location of samples. For instance, older homes are less likely to
have
vapor barriers incorporated into their foundation/slab construction, as
well as
more likely to develop cracks that allow for infiltration of vapors.
Earthen
floors and those of limestone provide increased opportunity for vapor
intrusion. Chronic wet basements are also a potential source of vapor
intrusion
as contaminants in dissolved groundwater can off-gas into the indoor
air.
It
is recommended that an upwind (from the building being sampled) outdoor
ambient
air sample be taken during every indoor air study to be used in the
final
evaluation of potential sources of chemicals in the indoor environment.
Generally, if background air is higher than risk-based values for
indoor air,
there is little point of mitigating indoor vapor intrusion. A finding
such as
this often suggests that efforts should be accelerated to remediate the
subsurface source of vapors.
For
there to be an accurate sample, products or operations that produce
vapors that
are being tested for must be removed from the building. These sources
include
cleaning products, hobby supplies, paints, recently dry-cleaned
clothes, and a
host of other common items, including gasoline stored in garages or
adjoining
structures. Even closed containers may release low, but measurable
levels of
target contaminants.
For
passive air sampling, exposure periods longer than one week may be
required.
Longer sampling periods may be difficult because of the expense, the
lack of
control over the situation (i.e., tampering or the addition
of variables or new sources by
unsupervised building occupants).
Sampling
equipment should be placed to minimize potential contamination from
extraneous
sources such as gasoline stations, automobiles, and other
gasoline-powered
engines, outdoor oil storage tanks, industrial facilities, etc.
EPA
suggests that if a building is located within 100 feet of a source
(either
vertically or laterally), vapor intrusion cannot be ruled out. In sites
that
overlie fractured bedrock or coarse-grained soils, that range may be
greater.
Petroleum
hydrocarbons (such as benzene) biodegrade well in unsaturated soils.
This
mechanism should be considered in the screening of buildings to be
sampled.
Unnecessary
ventilation should be avoided 24 hours prior to sampling.
Applicability
The
methods described are used to collect indoor and outdoor air samples.
Technology
Development Status
The
sampling methods described are all commercially available.
Web
Links
See http://www.mass.gov/dep/cleanup/laws/02-430.pdf
for an excellent description of various air-sampling protocols.
http://www.health.state.ny.us/environmental/indoors/air/guidance.htm
http://www.health.state.mn.us/divs/eh/hazardous/topics/iasampling.pdf
http://dhs.wi.gov/eh/Air/pdf/VI_guide.pdf
http://www.spawar.navy.mil/sti/publications/pubs/tr/1982/tr1982cond.pdf
http://www.serdp-estcp.org/Program-Areas/Environmental-Restoration/Contaminated-Groundwater/Emerging-Issues/ER-200423/ER-200423 for standard procedures.
http://www.epa.gov/Region06/6lab/taga.htm
http://www.srigc.com/ECDman.pdf
Other
Resources and Demonstrations
See "A
Stakeholder's Guide to Vapor Intrusion," by Lenny Siegel (see http://www.cpeo.org/pubs/SGVI.pdf).
See http://www.epa.gov/ttn/amtic/files/ambient/airtox/to-15r.pdf
for a description determination of ambient air concentrations,
primarily using
canisters.
See http://chromatographyonline.findanalytichem.com/lcgc/article/articleDetail.jsp?id=409516
for a detailed description of Electron-Capture Detectors (ECD). Also
see http://www.youtube.com/watch?v=d_6ON7TitTM
for a short animated explanation.
See http://www.itrcweb.org/Documents/VI-1.pdf
and http://www.epa.gov/nrmrl/pubs/600r08115/600r08115.pdf
for a full discussion of vapor intrusion technologies and regulatory
issues.
See also https://ert2.navfac.navy.mil/printfriendly.aspx?tool=VaporIntrusion and http://www.denix.osd.mil/references/upload/Tri-Serv_VI_Handbook_Final.pdf